NFPA CFPE Certified Fire Plan Examiner Exam Practice Test

Page: 1 / 14
Total 100 questions
Question 1

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 2

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 3

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 4

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 5

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 6

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 7

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Page:    1 / 14   
Total 100 questions