NFPA CFPE Certified Fire Plan Examiner Exam Practice Test

Page: 1 / 14
Total 100 questions
Question 1

What is the interior finish rating for exits in educational occupancies?



Answer : B

According to NFPA 101, Life Safety Code, the interior finish for exits in educational occupancies must be Class A or B. Class A finishes have the lowest flame spread and smoke development indices, while Class B finishes are also considered safe but slightly less restrictive than Class A. This requirement ensures that exit routes remain safe and clear in the event of a fire, facilitating rapid evacuation.


Question 2

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 3

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 4

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 5

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 6

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 7

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 8

What percentage of wall area may be covered with art work in a sprinklered educational occupancy?



Answer : C

According to NFPA 101, Life Safety Code, in a sprinklered educational occupancy, no more than 20% of the wall area may be covered with artwork or teaching materials to minimize fire hazards and ensure safe evacuation routes (NFPA 101, Section 14.7.4). This percentage is intended to balance educational needs with fire safety requirements.

Top of Form

Bottom of Form


Question 9

Which one of the following contains information describing construction materials such as doors windows, hardware, and finishes?



Answer : A

'Schedules' in architectural and construction documents refer to detailed lists that describe specific elements of the building, such as doors, windows, finishes, and hardware. These schedules provide essential information such as material type, size, color, finish, and other specifications necessary for construction and compliance with design standards.


Question 10

In positive alarm sequence systems trained personnel shall have a maximum of how many seconds during the alarm investigation phase to evaluate the fire condition and reset the system'?



Answer : C

According to NFPA 72, National Fire Alarm and Signaling Code, in positive alarm sequence systems, trained personnel have a maximum of 120 seconds (2 minutes) during the alarm investigation phase to evaluate the fire condition and reset the system. This time frame is provided to allow personnel to assess whether the alarm is legitimate or false before activating a full evacuation or emergency response.

Top of Form

Bottom of Form


Question 11

The responsibilities of a Board of Appeals includes which of the following?

I . Interpreting the codes

II . Reviewing alternative methods and procedures

III . Ruling on challenges to the building or fire official regarding the applicability and interpretation of the codes

IV . Evaluating alternative proposals for compliance with the codes



Answer : D

The Board of Appeals typically has several responsibilities, including interpreting the codes (I), reviewing alternative methods and procedures (II), ruling on challenges to the building or fire official regarding the applicability and interpretation of the codes (III), and evaluating alternative proposals for compliance with the codes (IV). These responsibilities ensure that the board provides a fair process for resolving disputes related to code enforcement and allows for alternative solutions that meet the intent of the codes.


Question 12

Which one of the following is NOT a typical reason to require construction permits and the review of plans by local government?



Answer : B

General traffic safety is not a typical reason for requiring construction permits and reviewing plans by local government. The primary reasons for requiring permits and plan reviews include ensuring community safety (A), emergency responder safety (C), and property conservation (D). These factors help to ensure that new construction complies with applicable codes and standards, reducing risks to life and property. General traffic safety is usually handled through separate traffic and transportation planning processes.


Question 13

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 14

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 15

What is the interior finish rating for exits in educational occupancies?



Answer : B

According to NFPA 101, Life Safety Code, the interior finish for exits in educational occupancies must be Class A or B. Class A finishes have the lowest flame spread and smoke development indices, while Class B finishes are also considered safe but slightly less restrictive than Class A. This requirement ensures that exit routes remain safe and clear in the event of a fire, facilitating rapid evacuation.


Question 16

What is the interior finish rating for exits in educational occupancies?



Answer : B

According to NFPA 101, Life Safety Code, the interior finish for exits in educational occupancies must be Class A or B. Class A finishes have the lowest flame spread and smoke development indices, while Class B finishes are also considered safe but slightly less restrictive than Class A. This requirement ensures that exit routes remain safe and clear in the event of a fire, facilitating rapid evacuation.


Question 17

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 18

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 19

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 20

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 21

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 22

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 23

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 24

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 25

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 26

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 27

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 28

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 29

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 30

What is the interior finish rating for exits in educational occupancies?



Answer : B

According to NFPA 101, Life Safety Code, the interior finish for exits in educational occupancies must be Class A or B. Class A finishes have the lowest flame spread and smoke development indices, while Class B finishes are also considered safe but slightly less restrictive than Class A. This requirement ensures that exit routes remain safe and clear in the event of a fire, facilitating rapid evacuation.


Question 31

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 32

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 33

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 34

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 35

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 36

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 37

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 38

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 39

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 40

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 41

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 42

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 43

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 44

What is the interior finish rating for exits in educational occupancies?



Answer : B

According to NFPA 101, Life Safety Code, the interior finish for exits in educational occupancies must be Class A or B. Class A finishes have the lowest flame spread and smoke development indices, while Class B finishes are also considered safe but slightly less restrictive than Class A. This requirement ensures that exit routes remain safe and clear in the event of a fire, facilitating rapid evacuation.


Question 45

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 46

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 47

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 48

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 49

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 50

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 51

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 52

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 53

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 54

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 55

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 56

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 57

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 58

What is the interior finish rating for exits in educational occupancies?



Answer : B

According to NFPA 101, Life Safety Code, the interior finish for exits in educational occupancies must be Class A or B. Class A finishes have the lowest flame spread and smoke development indices, while Class B finishes are also considered safe but slightly less restrictive than Class A. This requirement ensures that exit routes remain safe and clear in the event of a fire, facilitating rapid evacuation.


Question 59

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 60

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 61

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 62

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 63

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 64

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 65

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 66

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 67

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 68

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 69

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 70

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 71

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 72

What is the interior finish rating for exits in educational occupancies?



Answer : B

According to NFPA 101, Life Safety Code, the interior finish for exits in educational occupancies must be Class A or B. Class A finishes have the lowest flame spread and smoke development indices, while Class B finishes are also considered safe but slightly less restrictive than Class A. This requirement ensures that exit routes remain safe and clear in the event of a fire, facilitating rapid evacuation.


Question 73

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 74

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 75

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 76

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 77

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 78

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 79

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 80

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 81

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 82

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 83

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 84

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 85

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 86

What is the interior finish rating for exits in educational occupancies?



Answer : B

According to NFPA 101, Life Safety Code, the interior finish for exits in educational occupancies must be Class A or B. Class A finishes have the lowest flame spread and smoke development indices, while Class B finishes are also considered safe but slightly less restrictive than Class A. This requirement ensures that exit routes remain safe and clear in the event of a fire, facilitating rapid evacuation.


Question 87

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 88

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 89

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 90

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 91

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 92

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 93

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 94

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 95

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 96

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 97

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 98

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 99

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 100

What is the interior finish rating for exits in educational occupancies?



Answer : B

According to NFPA 101, Life Safety Code, the interior finish for exits in educational occupancies must be Class A or B. Class A finishes have the lowest flame spread and smoke development indices, while Class B finishes are also considered safe but slightly less restrictive than Class A. This requirement ensures that exit routes remain safe and clear in the event of a fire, facilitating rapid evacuation.


Question 101

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 102

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 103

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 104

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 105

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 106

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 107

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 108

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 109

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 110

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 111

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 112

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 113

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 114

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 115

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 116

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 117

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 118

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 119

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 120

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 121

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 122

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 123

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 124

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 125

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 126

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 127

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 128

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 129

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 130

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 131

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 132

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 133

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 134

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 135

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 136

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 137

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 138

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 139

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 140

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 141

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 142

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 143

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 144

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 145

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 146

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 147

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 148

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 149

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 150

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 151

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 152

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 153

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 154

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 155

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 156

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 157

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 158

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 159

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 160

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 161

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 162

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 163

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 164

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 165

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 166

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 167

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 168

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 169

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 170

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 171

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 172

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 173

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 174

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 175

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 176

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 177

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 178

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 179

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 180

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 181

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 182

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 183

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 184

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 185

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 186

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 187

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 188

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 189

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 190

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 191

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 192

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 193

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 194

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 195

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 196

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 197

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 198

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 199

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 200

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 201

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 202

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 203

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 204

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 205

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 206

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 207

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 208

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 209

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 210

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 211

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 212

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 213

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 214

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 215

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 216

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 217

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 218

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 219

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 220

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 221

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 222

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 223

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 224

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 225

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 226

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 227

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 228

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 229

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 230

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 231

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 232

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 233

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 234

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 235

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 236

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 237

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 238

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 239

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 240

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 241

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 242

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 243

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 244

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 245

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 246

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 247

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 248

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 249

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 250

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 251

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 252

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 253

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 254

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 255

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 256

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 257

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 258

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 259

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 260

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 261

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 262

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 263

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 264

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 265

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 266

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 267

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 268

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 269

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 270

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 271

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 272

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 273

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 274

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 275

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 276

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 277

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 278

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 279

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 280

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 281

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 282

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 283

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 284

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 285

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 286

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 287

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 288

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 289

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 290

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 291

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 292

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 293

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 294

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 295

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 296

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 297

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 298

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 299

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 300

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 301

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 302

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 303

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 304

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 305

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 306

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 307

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 308

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 309

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 310

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 311

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 312

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 313

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 314

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 315

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 316

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 317

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 318

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 319

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 320

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 321

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 322

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 323

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 324

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 325

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 326

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 327

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 328

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 329

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 330

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 331

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 332

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 333

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 334

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 335

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 336

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 337

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 338

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 339

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 340

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 341

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 342

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 343

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 344

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 345

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 346

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 347

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 348

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 349

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 350

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 351

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 352

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 353

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 354

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 355

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 356

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 357

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 358

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 359

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 360

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 361

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 362

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 363

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 364

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 365

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 366

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 367

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 368

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 369

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 370

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 371

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 372

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 373

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 374

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 375

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 376

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 377

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 378

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 379

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 380

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 381

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 382

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 383

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 384

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 385

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 386

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 387

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 388

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 389

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 390

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 391

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 392

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 393

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 394

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 395

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 396

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 397

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 398

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 399

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 400

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 401

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 402

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 403

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 404

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 405

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 406

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 407

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 408

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 409

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 410

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 411

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 412

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 413

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 414

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 415

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 416

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 417

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 418

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 419

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 420

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 421

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 422

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 423

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 424

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 425

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 426

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 427

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 428

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 429

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 430

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 431

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 432

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 433

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 434

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 435

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 436

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 437

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 438

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 439

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 440

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 441

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 442

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 443

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 444

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 445

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 446

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 447

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 448

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 449

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 450

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 451

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 452

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 453

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 454

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 455

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 456

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 457

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 458

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 459

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 460

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 461

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 462

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 463

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 464

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 465

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 466

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 467

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 468

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 469

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 470

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 471

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 472

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 473

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 474

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 475

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 476

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 477

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 478

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 479

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 480

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 481

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 482

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 483

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 484

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 485

On plan set A5 what does the number 19 in the box within kindergarten #3 pertain to?



Answer : C

The number '19' in the box within Kindergarten #3 on plan set A5 likely pertains to a specific element in the room's finish schedule, which is usually denoted by a number corresponding to a finish material or treatment. In architectural plans, such numbers typically refer to walls, ceilings, floors, or base finishes. Based on standard conventions, '19' appears to be associated with 'walls,' referencing a particular type of wall finish or material specified in the plan's legend.

Top of Form

Bottom of Form


Question 486

Exhibit.

According to plan sheet F01, hydraulic calculations must be based on flow criteria obtained by new flow tests conducted by which one of the following?



Answer : C

Hydraulic calculations for fire protection systems, such as sprinklers, must be based on accurate flow and pressure data. This data is often obtained from flow tests conducted by the local fire department. The fire department has the authority and expertise to perform flow tests on public water supplies, ensuring that the data is reliable and reflects the actual conditions under which the sprinkler system must operate.


Question 487

Which of the following would not require having to submit construction documents for all fire protection systems and the issuance of a permit by the AHJ?



Answer : A

According to NFPA 1031, construction documents for all fire protection systems and permits issued by the Authority Having Jurisdiction (AHJ) are necessary for rehabilitation, installation, and modification processes. However, an acceptance test, which is the final inspection and verification conducted by the AHJ to ensure the system meets all operational criteria, does not require prior submission of documents for fire protection systems or issuance of a permit. This process is done after installation or modification is complete to confirm compliance with fire codes and standards. Thus, option A is the correct answer.

Top of Form

Bottom of Form


Question 488

Exhibit.

On plan A7, what is the corridor floor finish for the first floor plan wing C?



Answer : B

Upon examining Plan A7, it is identified that the corridor floor finish for the first-floor plan wing C is labeled as 'Ceramic tile.' The NFPA 1031 outlines that the Plan Examiner must confirm that the materials used in construction meet fire resistance, durability, and safety requirements. Ceramic tile is a preferred choice for its fire-resistant properties and compliance with safety regulations.


Question 489

Plan examiners should be aware of what two basic types of code models'?



Answer : D

The two basic types of code models are 'Prescriptive' and 'Performance.' Prescriptive codes provide specific requirements that must be followed, such as construction materials, methods, and dimensions. Performance codes, on the other hand, focus on the desired outcomes or objectives, allowing for more flexibility in how compliance is achieved. Plan examiners should understand both types to evaluate compliance effectively during plan reviews.


Question 490

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 491

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 492

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 493

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 494

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 495

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 496

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 497

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 498

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 499

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 500

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 501

A 4 in. (101.6 mm) riser requires what minimum diameter pipe for the combination mam drain and alarm test connection?



Answer : B

For a 4-inch (101.6 mm) riser, the minimum diameter pipe for the combination main drain and alarm test connection should be 1 inch (25.4 mm). This size is specified to ensure adequate water flow during a test or when draining the system, in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems.


Question 502

Exhibit.

How many different sprinkler types are shown on plan F0.1?



Answer : C

Based on the symbols and descriptions on plan F0.1, there are 5 different sprinkler types shown. These may include various types such as upright, pendant, sidewall, dry, and recessed sprinklers, each serving different functions and locations within the building. The specific types and their designations are typically detailed in the fire protection legend or key on the plan.


Question 503

New manual fire alarm boxes must be within what distance from the door?



Answer : A

New manual fire alarm boxes must be installed within 60 inches (1,524 mm) from the door, according to NFPA 72, National Fire Alarm and Signaling Code. This placement ensures that the alarm is easily accessible and visible for occupants as they exit, facilitating prompt alarm activation in case of fire or emergency.

Top of Form

Bottom of Form


Question 504

For the purposes of fire sprinkler protection, occupancies where combustibility is low. quantity of combustibles is moderate, and stockpiles of combustibles do not exceed 8 ft (2.4 m). are called



Answer : B

Occupancies where the combustibility is low, the quantity of combustibles is moderate, and stockpiles of combustibles do not exceed 8 feet (2.4 meters) are classified as 'Ordinary hazard (Group 1).' This classification, as defined in NFPA 13, Standard for the Installation of Sprinkler Systems, is used to determine the design density and spacing of sprinklers required to provide adequate fire protection.


Question 505

Where would you find information pertaining to the seismic load?



Answer : A

Information pertaining to seismic loads would be found in the structural plans. These plans contain details about the building's framework and its ability to resist seismic forces. The structural plans include calculations and specifications that ensure the building's integrity under seismic stress, following relevant codes such as the International Building Code (IBC) and NFPA 5000.


Question 506

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 507

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 508

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 509

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 510

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 511

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 512

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 513

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 514

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 515

A 4 in. (101.6 mm) riser requires what minimum diameter pipe for the combination mam drain and alarm test connection?



Answer : B

For a 4-inch (101.6 mm) riser, the minimum diameter pipe for the combination main drain and alarm test connection should be 1 inch (25.4 mm). This size is specified to ensure adequate water flow during a test or when draining the system, in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems.


Question 516

Exhibit.

How many different sprinkler types are shown on plan F0.1?



Answer : C

Based on the symbols and descriptions on plan F0.1, there are 5 different sprinkler types shown. These may include various types such as upright, pendant, sidewall, dry, and recessed sprinklers, each serving different functions and locations within the building. The specific types and their designations are typically detailed in the fire protection legend or key on the plan.


Question 517

New manual fire alarm boxes must be within what distance from the door?



Answer : A

New manual fire alarm boxes must be installed within 60 inches (1,524 mm) from the door, according to NFPA 72, National Fire Alarm and Signaling Code. This placement ensures that the alarm is easily accessible and visible for occupants as they exit, facilitating prompt alarm activation in case of fire or emergency.

Top of Form

Bottom of Form


Question 518

For the purposes of fire sprinkler protection, occupancies where combustibility is low. quantity of combustibles is moderate, and stockpiles of combustibles do not exceed 8 ft (2.4 m). are called



Answer : B

Occupancies where the combustibility is low, the quantity of combustibles is moderate, and stockpiles of combustibles do not exceed 8 feet (2.4 meters) are classified as 'Ordinary hazard (Group 1).' This classification, as defined in NFPA 13, Standard for the Installation of Sprinkler Systems, is used to determine the design density and spacing of sprinklers required to provide adequate fire protection.


Question 519

Where would you find information pertaining to the seismic load?



Answer : A

Information pertaining to seismic loads would be found in the structural plans. These plans contain details about the building's framework and its ability to resist seismic forces. The structural plans include calculations and specifications that ensure the building's integrity under seismic stress, following relevant codes such as the International Building Code (IBC) and NFPA 5000.


Question 520

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 521

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 522

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 523

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 524

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 525

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 526

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 527

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 528

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 529

A 4 in. (101.6 mm) riser requires what minimum diameter pipe for the combination mam drain and alarm test connection?



Answer : B

For a 4-inch (101.6 mm) riser, the minimum diameter pipe for the combination main drain and alarm test connection should be 1 inch (25.4 mm). This size is specified to ensure adequate water flow during a test or when draining the system, in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems.


Question 530

Exhibit.

How many different sprinkler types are shown on plan F0.1?



Answer : C

Based on the symbols and descriptions on plan F0.1, there are 5 different sprinkler types shown. These may include various types such as upright, pendant, sidewall, dry, and recessed sprinklers, each serving different functions and locations within the building. The specific types and their designations are typically detailed in the fire protection legend or key on the plan.


Question 531

New manual fire alarm boxes must be within what distance from the door?



Answer : A

New manual fire alarm boxes must be installed within 60 inches (1,524 mm) from the door, according to NFPA 72, National Fire Alarm and Signaling Code. This placement ensures that the alarm is easily accessible and visible for occupants as they exit, facilitating prompt alarm activation in case of fire or emergency.

Top of Form

Bottom of Form


Question 532

For the purposes of fire sprinkler protection, occupancies where combustibility is low. quantity of combustibles is moderate, and stockpiles of combustibles do not exceed 8 ft (2.4 m). are called



Answer : B

Occupancies where the combustibility is low, the quantity of combustibles is moderate, and stockpiles of combustibles do not exceed 8 feet (2.4 meters) are classified as 'Ordinary hazard (Group 1).' This classification, as defined in NFPA 13, Standard for the Installation of Sprinkler Systems, is used to determine the design density and spacing of sprinklers required to provide adequate fire protection.


Question 533

Where would you find information pertaining to the seismic load?



Answer : A

Information pertaining to seismic loads would be found in the structural plans. These plans contain details about the building's framework and its ability to resist seismic forces. The structural plans include calculations and specifications that ensure the building's integrity under seismic stress, following relevant codes such as the International Building Code (IBC) and NFPA 5000.


Question 534

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 535

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 536

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 537

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 538

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 539

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 540

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 541

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 542

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 543

A 4 in. (101.6 mm) riser requires what minimum diameter pipe for the combination mam drain and alarm test connection?



Answer : B

For a 4-inch (101.6 mm) riser, the minimum diameter pipe for the combination main drain and alarm test connection should be 1 inch (25.4 mm). This size is specified to ensure adequate water flow during a test or when draining the system, in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems.


Question 544

Exhibit.

How many different sprinkler types are shown on plan F0.1?



Answer : C

Based on the symbols and descriptions on plan F0.1, there are 5 different sprinkler types shown. These may include various types such as upright, pendant, sidewall, dry, and recessed sprinklers, each serving different functions and locations within the building. The specific types and their designations are typically detailed in the fire protection legend or key on the plan.


Question 545

New manual fire alarm boxes must be within what distance from the door?



Answer : A

New manual fire alarm boxes must be installed within 60 inches (1,524 mm) from the door, according to NFPA 72, National Fire Alarm and Signaling Code. This placement ensures that the alarm is easily accessible and visible for occupants as they exit, facilitating prompt alarm activation in case of fire or emergency.

Top of Form

Bottom of Form


Question 546

For the purposes of fire sprinkler protection, occupancies where combustibility is low. quantity of combustibles is moderate, and stockpiles of combustibles do not exceed 8 ft (2.4 m). are called



Answer : B

Occupancies where the combustibility is low, the quantity of combustibles is moderate, and stockpiles of combustibles do not exceed 8 feet (2.4 meters) are classified as 'Ordinary hazard (Group 1).' This classification, as defined in NFPA 13, Standard for the Installation of Sprinkler Systems, is used to determine the design density and spacing of sprinklers required to provide adequate fire protection.


Question 547

Where would you find information pertaining to the seismic load?



Answer : A

Information pertaining to seismic loads would be found in the structural plans. These plans contain details about the building's framework and its ability to resist seismic forces. The structural plans include calculations and specifications that ensure the building's integrity under seismic stress, following relevant codes such as the International Building Code (IBC) and NFPA 5000.


Question 548

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 549

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 550

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 551

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 552

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 553

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 554

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 555

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 556

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 557

A 4 in. (101.6 mm) riser requires what minimum diameter pipe for the combination mam drain and alarm test connection?



Answer : B

For a 4-inch (101.6 mm) riser, the minimum diameter pipe for the combination main drain and alarm test connection should be 1 inch (25.4 mm). This size is specified to ensure adequate water flow during a test or when draining the system, in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems.


Question 558

Exhibit.

How many different sprinkler types are shown on plan F0.1?



Answer : C

Based on the symbols and descriptions on plan F0.1, there are 5 different sprinkler types shown. These may include various types such as upright, pendant, sidewall, dry, and recessed sprinklers, each serving different functions and locations within the building. The specific types and their designations are typically detailed in the fire protection legend or key on the plan.


Question 559

New manual fire alarm boxes must be within what distance from the door?



Answer : A

New manual fire alarm boxes must be installed within 60 inches (1,524 mm) from the door, according to NFPA 72, National Fire Alarm and Signaling Code. This placement ensures that the alarm is easily accessible and visible for occupants as they exit, facilitating prompt alarm activation in case of fire or emergency.

Top of Form

Bottom of Form


Question 560

For the purposes of fire sprinkler protection, occupancies where combustibility is low. quantity of combustibles is moderate, and stockpiles of combustibles do not exceed 8 ft (2.4 m). are called



Answer : B

Occupancies where the combustibility is low, the quantity of combustibles is moderate, and stockpiles of combustibles do not exceed 8 feet (2.4 meters) are classified as 'Ordinary hazard (Group 1).' This classification, as defined in NFPA 13, Standard for the Installation of Sprinkler Systems, is used to determine the design density and spacing of sprinklers required to provide adequate fire protection.


Question 561

Where would you find information pertaining to the seismic load?



Answer : A

Information pertaining to seismic loads would be found in the structural plans. These plans contain details about the building's framework and its ability to resist seismic forces. The structural plans include calculations and specifications that ensure the building's integrity under seismic stress, following relevant codes such as the International Building Code (IBC) and NFPA 5000.


Question 562

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 563

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 564

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 565

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 566

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 567

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 568

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 569

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 570

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 571

A 4 in. (101.6 mm) riser requires what minimum diameter pipe for the combination mam drain and alarm test connection?



Answer : B

For a 4-inch (101.6 mm) riser, the minimum diameter pipe for the combination main drain and alarm test connection should be 1 inch (25.4 mm). This size is specified to ensure adequate water flow during a test or when draining the system, in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems.


Question 572

Exhibit.

How many different sprinkler types are shown on plan F0.1?



Answer : C

Based on the symbols and descriptions on plan F0.1, there are 5 different sprinkler types shown. These may include various types such as upright, pendant, sidewall, dry, and recessed sprinklers, each serving different functions and locations within the building. The specific types and their designations are typically detailed in the fire protection legend or key on the plan.


Question 573

New manual fire alarm boxes must be within what distance from the door?



Answer : A

New manual fire alarm boxes must be installed within 60 inches (1,524 mm) from the door, according to NFPA 72, National Fire Alarm and Signaling Code. This placement ensures that the alarm is easily accessible and visible for occupants as they exit, facilitating prompt alarm activation in case of fire or emergency.

Top of Form

Bottom of Form


Question 574

For the purposes of fire sprinkler protection, occupancies where combustibility is low. quantity of combustibles is moderate, and stockpiles of combustibles do not exceed 8 ft (2.4 m). are called



Answer : B

Occupancies where the combustibility is low, the quantity of combustibles is moderate, and stockpiles of combustibles do not exceed 8 feet (2.4 meters) are classified as 'Ordinary hazard (Group 1).' This classification, as defined in NFPA 13, Standard for the Installation of Sprinkler Systems, is used to determine the design density and spacing of sprinklers required to provide adequate fire protection.


Question 575

Where would you find information pertaining to the seismic load?



Answer : A

Information pertaining to seismic loads would be found in the structural plans. These plans contain details about the building's framework and its ability to resist seismic forces. The structural plans include calculations and specifications that ensure the building's integrity under seismic stress, following relevant codes such as the International Building Code (IBC) and NFPA 5000.


Question 576

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 577

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 578

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 579

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 580

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 581

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 582

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 583

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 584

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 585

A 4 in. (101.6 mm) riser requires what minimum diameter pipe for the combination mam drain and alarm test connection?



Answer : B

For a 4-inch (101.6 mm) riser, the minimum diameter pipe for the combination main drain and alarm test connection should be 1 inch (25.4 mm). This size is specified to ensure adequate water flow during a test or when draining the system, in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems.


Question 586

Exhibit.

How many different sprinkler types are shown on plan F0.1?



Answer : C

Based on the symbols and descriptions on plan F0.1, there are 5 different sprinkler types shown. These may include various types such as upright, pendant, sidewall, dry, and recessed sprinklers, each serving different functions and locations within the building. The specific types and their designations are typically detailed in the fire protection legend or key on the plan.


Question 587

New manual fire alarm boxes must be within what distance from the door?



Answer : A

New manual fire alarm boxes must be installed within 60 inches (1,524 mm) from the door, according to NFPA 72, National Fire Alarm and Signaling Code. This placement ensures that the alarm is easily accessible and visible for occupants as they exit, facilitating prompt alarm activation in case of fire or emergency.

Top of Form

Bottom of Form


Question 588

For the purposes of fire sprinkler protection, occupancies where combustibility is low. quantity of combustibles is moderate, and stockpiles of combustibles do not exceed 8 ft (2.4 m). are called



Answer : B

Occupancies where the combustibility is low, the quantity of combustibles is moderate, and stockpiles of combustibles do not exceed 8 feet (2.4 meters) are classified as 'Ordinary hazard (Group 1).' This classification, as defined in NFPA 13, Standard for the Installation of Sprinkler Systems, is used to determine the design density and spacing of sprinklers required to provide adequate fire protection.


Question 589

Where would you find information pertaining to the seismic load?



Answer : A

Information pertaining to seismic loads would be found in the structural plans. These plans contain details about the building's framework and its ability to resist seismic forces. The structural plans include calculations and specifications that ensure the building's integrity under seismic stress, following relevant codes such as the International Building Code (IBC) and NFPA 5000.


Question 590

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 591

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 592

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 593

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 594

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 595

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 596

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Question 597

What is the maximum number of stones below grade that may be occupied for a non-sprinklered assembly occupancy of Type III (211) construction?



Answer : B

According to NFPA 101, Life Safety Code, for a non-sprinklered assembly occupancy of Type III (211) construction, only one story below grade may be occupied. This limitation is intended to ensure safe egress for occupants during an emergency. Additional levels below grade increase the risk and complexity of evacuation, especially in the absence of an automatic sprinkler system.


Question 598

Exhibit.

On plan C1 what is the width of the fire department access driveway on the south facing side of the building wing closes! lo Bedford Street?



Answer : B


Question 599

A 4 in. (101.6 mm) riser requires what minimum diameter pipe for the combination mam drain and alarm test connection?



Answer : B

For a 4-inch (101.6 mm) riser, the minimum diameter pipe for the combination main drain and alarm test connection should be 1 inch (25.4 mm). This size is specified to ensure adequate water flow during a test or when draining the system, in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems.


Question 600

Exhibit.

How many different sprinkler types are shown on plan F0.1?



Answer : C

Based on the symbols and descriptions on plan F0.1, there are 5 different sprinkler types shown. These may include various types such as upright, pendant, sidewall, dry, and recessed sprinklers, each serving different functions and locations within the building. The specific types and their designations are typically detailed in the fire protection legend or key on the plan.


Question 601

New manual fire alarm boxes must be within what distance from the door?



Answer : A

New manual fire alarm boxes must be installed within 60 inches (1,524 mm) from the door, according to NFPA 72, National Fire Alarm and Signaling Code. This placement ensures that the alarm is easily accessible and visible for occupants as they exit, facilitating prompt alarm activation in case of fire or emergency.

Top of Form

Bottom of Form


Question 602

For the purposes of fire sprinkler protection, occupancies where combustibility is low. quantity of combustibles is moderate, and stockpiles of combustibles do not exceed 8 ft (2.4 m). are called



Answer : B

Occupancies where the combustibility is low, the quantity of combustibles is moderate, and stockpiles of combustibles do not exceed 8 feet (2.4 meters) are classified as 'Ordinary hazard (Group 1).' This classification, as defined in NFPA 13, Standard for the Installation of Sprinkler Systems, is used to determine the design density and spacing of sprinklers required to provide adequate fire protection.


Question 603

Where would you find information pertaining to the seismic load?



Answer : A

Information pertaining to seismic loads would be found in the structural plans. These plans contain details about the building's framework and its ability to resist seismic forces. The structural plans include calculations and specifications that ensure the building's integrity under seismic stress, following relevant codes such as the International Building Code (IBC) and NFPA 5000.


Question 604

The symbol above is a representation of which one of the following?



Answer : A

In the context of NFPA standards, particularly NFPA 1031, 'Standard for Professional Qualifications for Fire Inspector and Plan Examiner,' the symbol that represents a 'Fire hydrant' is universally recognized in fire protection systems. NFPA 1031 outlines various competencies and knowledge areas required for fire inspectors and plan examiners, including understanding symbols and terminology related to fire protection systems.

Reference from NFPA 1031: NFPA 1031 emphasizes that fire inspectors and plan examiners must be familiar with different components of fire protection systems, which includes being able to identify symbols used in construction and fire safety plans. Symbols such as those representing fire hydrants, risers, floor drains, and utility meters are part of the essential knowledge for professionals in this field to ensure compliance with fire codes and standards during plan reviews (NFPA 1031, Section 4.2.1 - Understanding of fire protection systems and their components).

Understanding and correctly identifying these symbols is crucial for maintaining effective fire safety and ensuring the correct placement and functioning of fire protection equipment. The fire hydrant symbol, in particular, is a key element in fire protection drawings and plans, indicating the location of hydrants that provide water supply to firefighters in the event of a fire.


Question 605

Exhibit.

What is the construction type specified for the new addition for plan set Tl?



Answer : B

The construction type specified for the new addition in plan set T1 is Type II (000). This construction type, as defined in the International Building Code (IBC), refers to buildings with non-combustible materials for all structural elements, but with no fire-resistance rating requirements for any of the structural components. This is typical for newer additions where fire safety is achieved through non-combustible materials and other fire protection systems, such as sprinklers.

Top of Form

Bottom of Form


Question 606

What is the minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier?



Answer : C

The minimum required rating for a fire door assembly installed in a 2-hour rated fire barrier is 1-1/2 hours. According to NFPA 80, Standard for Fire Doors and Other Opening Protectives, fire door assemblies are typically rated at three-quarters of the rating of the wall in which they are installed. Thus, a 2-hour rated wall requires a 1-1/2-hour fire door assembly.


Question 607

What is the maximum spacing for standard pendent sprinklers for light hazard occupancies that are hydraulically calculated?



Answer : C

The maximum spacing for standard pendent sprinklers in light hazard occupancies that are hydraulically calculated is 15 feet (4.6 meters). This spacing complies with NFPA 13, which provides the design requirements for sprinkler systems, ensuring adequate coverage and water distribution to control or extinguish a fire in light hazard areas.


Question 608

What is the permitted fire flow reduction for two buildings on the same lot with a separation of 40 ft (12 m)?



Answer : A

For two buildings on the same lot with a separation of 40 ft (12 m), a fire flow reduction of 25 percent is permitted. This reduction is typically allowed under the guidelines of NFPA standards or local fire codes, which consider the distance between structures and the associated fire risk. A separation of 40 feet is sufficient to warrant a 25 percent reduction in required fire flow, assuming that other fire safety measures, such as sprinkler systems, are in place.


Question 609

Exhibit.

Based on site plan C1 of the plan set what is the maximum depth the water lines are to be buried''



Answer : A

Based on site plan C1 of the plan set, the maximum depth for burying the water lines is 4 feet (1.2 meters). This depth is typically required to protect the pipes from freezing temperatures and mechanical damage while ensuring compliance with local codes and standards for water line installation.

Top of Form

Bottom of Form


Question 610

Fire alarm indicating appliances shall be located a minimum of how many inches below finished ceilings?



Answer : A

Fire alarm indicating appliances must be located a minimum of 4 inches (102 mm) below finished ceilings. This clearance ensures that the devices are not obstructed by ceiling-mounted structures and can properly notify occupants in case of an emergency, as specified by NFPA 72, National Fire Alarm and Signaling Code.


Page:    1 / 14   
Total 100 questions